| POWER CABLES |
| REFERENCE
STANDARDS |
|
»
INTERNATIONAL :
»
NATIONAL :
|
BS 6346, IEC 60502
IS 1554, IS 7098 |
| VOLTAGE RATING |
1.1 KV, 3.3 KV, 6.6 KV & 11 KV. |
| CONDUCTOR |
COPPER/ALUMINIUM |
| INSULATION |
PVC/XLPE |
| ARMOUR |
G.I WIRE/STEEL STRIP/STEEL TAPE |
| INNER/OUTER SHEATH |
PVC/FR PVC/FRLS PVC/ZH FRLS COMPOUNDS
|
| Single-core
600/1000 V cables with circular standed copper conductors
- BS 6346 |
| 1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
Nominal
cross-
sectional
area of
conductor* |
Thickness
of
insulation |
Unarmoured cables |
Armoured cables |
Thickness
of sheath |
Approx-
imate
overall
diameter |
Thickness
of extruded
bedding |
Nominal
armour
wire
diameter |
Thickness
of
oversheath |
Approx-
imate
overall
diameter |
| mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
| 50 |
1.4 |
1.4 |
15.1 |
0.8 |
1.25 |
1.5 |
19.1 |
| 70 |
1.4 |
1.4 |
16.9 |
0.8 |
1.25 |
1.6 |
21.1 |
| 95 |
1.6 |
1.5 |
19.4 |
0.8 |
1.25 |
1.6 |
23.4 |
| 120 |
1.6 |
1.5 |
21.0 |
1.0 |
1.6 |
1.7 |
26.3 |
| 150 |
1.8 |
1.6 |
23.2 |
1.0 |
1.6 |
1.7 |
28.3 |
| 185 |
2.0 |
1.7 |
25.8 |
1.0 |
1.6 |
1.8 |
30.8 |
| 240 |
2.2 |
1.8 |
29.0 |
1.0 |
1.6 |
1.9 |
34.1 |
| 300 |
2.4 |
1.9 |
32.1 |
1.0 |
1.6 |
1.9 |
37.0 |
| 400 |
2.6 |
2.0 |
35.8 |
1.2 |
2.0 |
2.1 |
42.0 |
| 500 |
2.8 |
2.1 |
39.6 |
1.2 |
2.0 |
2.1 |
45.6 |
| 630 |
2.8 |
2.2 |
43.8 |
1.2 |
2.0 |
2.2 |
49.7 |
| 800 |
2.8 |
2.3 |
48.3 |
1.4 |
2.5 |
2.4 |
55.8 |
| 1000 |
3.0 |
2.5 |
53.7 |
1.4 |
2.5 |
2.5 |
61.0 |
| Two-core
600/1000 V cables with copper conductors - BS 6346 |
| 1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
Nominal
cross-
sectional
area of
cond-
uctor* |
Thickness
of
insulation |
Unarmoured
cables |
Armoured
cables |
Thickness
of sheath |
Approx-
imate
overall
diameter |
Thickness
of extruded
bedding |
Nominal
armour
wire
diameter |
Thickness
of
over-
sheath |
Approximate
overall diameter |
Extruded
bedding |
Tapped
bedding |
| mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
| 1.5* |
0.6 |
- |
- |
0.8 |
0.9 |
1.3 |
11.7 |
- |
| 1.5† |
0.6 |
- |
- |
0.8 |
0.9 |
1.4 |
12.3 |
- |
| 2.5* |
0.7 |
- |
- |
0.8 |
0.9 |
1.4 |
13.1 |
- |
| 2.5† |
0.7 |
- |
- |
0.8 |
0.9 |
1.4 |
13.6 |
- |
| 4† |
0.8 |
- |
- |
0.8 |
0.9 |
1.4 |
15.1 |
- |
| 6† |
0.8 |
- |
- |
0.8 |
1.25 |
1.5 |
16.5 |
- |
| 10† |
1.0 |
1.8 |
16.1 |
0.8 |
1.25 |
1.6 |
20.1 |
20.1 |
| 16† |
1.0 |
1.8 |
18.6 |
0.8 |
1.25 |
1.6 |
21.9 |
21.9 |
| 25‡ |
1.2 |
1.8 |
18.4 |
1.0 |
1.6 |
1.7 |
23.0 |
22.6 |
| 25† |
1.2 |
1.8 |
22.1 |
1.0 |
1.6 |
1.7 |
26.7 |
26.3 |
| 35‡ |
1.2 |
1.8 |
20.1 |
1.0 |
1.6 |
1.8 |
24.9 |
24.5 |
| 35† |
1.2 |
1.8 |
24.5 |
1.0 |
1.6 |
1.8 |
29.4 |
29.0 |
| 50§ |
1.4 |
1.8 |
22.8 |
1.0 |
1.6 |
1.9 |
27.8 |
27.4 |
| 70 |
1.4 |
1.9 |
25.5 |
1.2 |
1.6 |
1.9 |
30.4 |
30.4 |
| 95 |
1.6 |
2.0 |
29.3 |
1.2 |
2.0 |
2.1 |
35.5 |
34.7 |
| 120 |
1.6 |
2.1 |
31.8 |
1.2 |
2.0 |
2.2 |
38.0 |
37.2 |
| 150 |
1.8 |
2.2 |
35.1 |
1.2 |
2.0 |
2.3 |
41.3 |
40.5 |
| 185 |
2.0 |
2.4 |
39.1 |
1.4 |
2.5 |
2.4 |
46.4 |
45.2 |
| 240 |
2.2 |
2.5 |
43.9 |
1.4 |
2.5 |
2.5 |
51.2 |
50.0 |
| 300 |
2.4 |
2.7 |
48.7 |
1.6 |
2.5 |
2.7 |
56.4 |
54.8 |
| 400 |
2.6 |
2.9 |
54.2 |
1.6 |
2.5 |
2.9 |
61.9 |
60.3 |
* Circular solid conductors (class 1). † Circular
or circular compacted stranded conductors (class 2).
‡ Shaped stranded conductors (class 2) §
Cables having conductors of nominal cross-sectional area
50 mm2 and above have shaped stranded conductors
(class 2). |
| Three-core
600/1000 V cables with copper conductors - BS 6346 |
| 1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
Nominal
cross-
sectional
area of
cond-
uctor* |
Thickness
of
insulation |
Unarmoured
cables |
Armoured
cables |
Thickness
of sheath |
Approx-
imate
overall
diameter |
Thickness
of extruded
bedding |
Nominal
armour
wire
diameter |
Thickness
of
over-
sheath |
Approximate
overall diameter |
Extruded
bedding |
Tapped
bedding |
| mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
| 1.5* |
0.6 |
- |
- |
0.8 |
0.9 |
1.4 |
12.3 |
- |
| 1.5† |
0.6 |
- |
- |
0.8 |
0.9 |
1.4 |
12.8 |
- |
| 2.5* |
0.7 |
- |
- |
0.8 |
0.9 |
1.4 |
13.6 |
- |
| 2.5† |
0.7 |
- |
- |
0.8 |
0.9 |
1.4 |
14.1 |
- |
| 4† |
0.8 |
- |
- |
0.8 |
0.9 |
1.4 |
15.8 |
- |
| 6† |
0.8 |
- |
- |
0.8 |
1.25 |
1.5 |
18.0 |
- |
| 10† |
1.0 |
1.8 |
17.0 |
0.8 |
1.25 |
1.6 |
21.2 |
21.2 |
| 16† |
1.0 |
1.8 |
19.7 |
0.8 |
1.25 |
1.6 |
23.1 |
23.1 |
| 25‡ |
1.2 |
1.8 |
20.4 |
1.0 |
1.6 |
1.7 |
25.0 |
24.6 |
| 25† |
1.2 |
1.8 |
23.5 |
1.0 |
1.6 |
1.7 |
28.2 |
27.8 |
| 35‡ |
1.2 |
1.8 |
22.4 |
1.0 |
1.6 |
1.8 |
27.3 |
26.9 |
| 35† |
1.2 |
1.8 |
26.2 |
1.0 |
1.6 |
1.8 |
31.0 |
30.6 |
| 50§ |
1.4 |
1.8 |
25.5 |
1.0 |
1.6 |
1.9 |
30.5 |
30.1 |
| 70 |
1.4 |
1.9 |
28.7 |
1.2 |
2.0 |
2.0 |
35.0 |
34.2 |
| 95 |
1.6 |
2.1 |
33.3 |
1.2 |
2.0 |
2.1 |
39.3 |
38.5 |
| 120 |
1.6 |
2.2 |
36.3 |
1.2 |
2.0 |
2.2 |
42.2 |
41.4 |
| 150 |
1.8 |
2.3 |
40.0 |
1.4 |
2.5 |
2.4 |
47.5 |
46.3 |
| 185 |
2.0 |
2.5 |
44.6 |
1.4 |
2.5 |
2.5 |
51.9 |
50.7 |
| 240 |
2.2 |
2.6 |
50.1 |
1.6 |
2.5 |
2.6 |
57.8 |
56.2 |
| 300 |
2.4 |
2.8 |
55.6 |
1.6 |
2.5 |
2.8 |
63.2 |
61.6 |
| 400 |
2.6 |
3.1 |
62.2 |
1.6 |
2.5 |
3.0 |
69.6 |
68.0 |
* Circular solid conductors (class 1).
† Circular or circular compacted stranded conductors
(class 2).
‡ Shaped stranded conductors (class 2)
§ Cables having conductors of nominal cross-sectional
area 50 mm2 and above have shaped stranded
conductors (class 2). |
| Fore-core
600/1000 V cables with copper conductors - BS 6346 |
| 1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
Nominal
cross-
sectional
area of
cond-
uctor* |
Thickness
of
insulation |
Unarmoured
cables |
Armoured
cables |
Thickness
of sheath |
Approx-
imate
overall
diameter |
Thickness
of extruded
bedding |
Nominal
armour
wire
diameter |
Thickness
of
over-
sheath |
Approximate
overall diameter |
Extruded
bedding |
Tapped
bedding |
| mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
| 1.5* |
0.6 |
- |
- |
0.8 |
0.9 |
1.4 |
13.0 |
- |
| 1.5† |
0.6 |
- |
- |
0.8 |
0.9 |
1.4 |
13.5 |
- |
| 2.5* |
0.7 |
- |
- |
0.8 |
0.9 |
1.4 |
14.5 |
- |
| 2.5† |
0.7 |
- |
- |
0.8 |
0.9 |
1.4 |
15.0 |
- |
| 4† |
0.8 |
- |
- |
0.8 |
1.25 |
1.5 |
17.8 |
- |
| 6† |
0.8 |
- |
- |
0.8 |
1.25 |
1.5 |
19.2 |
- |
| 10† |
1.0 |
1.8 |
18.6 |
0.8 |
1.25 |
1.6 |
22.8 |
22.8 |
| 16† |
1.0 |
1.8 |
21.6 |
1.0 |
1.6 |
1.7 |
26.3 |
25.9 |
| 25‡ |
1.2 |
1.8 |
22.9 |
1.0 |
1.6 |
1.8 |
27.8 |
27.4 |
| 25† |
1.2 |
1.8 |
25.9 |
1.0 |
1.6 |
1.8 |
30.7 |
30.3 |
| 35‡ |
1.2 |
1.8 |
25.4 |
1.0 |
1.6 |
1.9 |
30.5 |
30.1 |
| 35† |
1.2 |
1.8 |
28.9 |
1.0 |
1.6 |
1.9 |
33.9 |
33.5 |
| 50§ |
1.4 |
1.9 |
29.2 |
1.2 |
2.0 |
2.0 |
35.4 |
34.6 |
| 70 |
1.4 |
2.0 |
33.0 |
1.2 |
2.0 |
2.1 |
39.2 |
38.4 |
| 95 |
1.6 |
2.2 |
38.3 |
1.2 |
2.0 |
2.2 |
44.3 |
43.5 |
| 120 |
1.6 |
2.3 |
41.8 |
1.4 |
2.5 |
2.4 |
49.3 |
48.1 |
| 150 |
1.8 |
2.5 |
46.3 |
1.4 |
2.5 |
2.5 |
53.6 |
52.4 |
| 185 |
2.0 |
2.6 |
51.3 |
1.6 |
2.5 |
2.6 |
59.0 |
57.4 |
| 240 |
2.2 |
2.8 |
58.0 |
1.6 |
2.5 |
2.8 |
65.7 |
64.1 |
| 300 |
2.4 |
3.1 |
64.6 |
1.6 |
2.5 |
3.0 |
72.0 |
70.4 |
| 400 |
2.6 |
3.3 |
72.0 |
1.8 |
3.15 |
3.3 |
81.3 |
79.3 |
* Circular solid conductors (class 1).
† Circular or circular compacted stranded conductors
(class 2).
‡ Shaped stranded conductors (class 2) §
Cables having conductors of nominal cross-sectional area
50 mm2 and above have shaped stranded conductors
(class 2). |