1100 volts four core with reduced Neutral Core Unarmoured/Armoured Cable Type A YY/A YFY to IS : 1554 (part-I) 1988.
Nominal conductor
area
(sq.mm.) 25/16 35/16 50/25 70/35 95/50 12/70 150/70 185/95 240/120 300/150 400/185
Unarmoured AYY
Nom. insulation
thickness
mm 12/1.0 12/1.0 14/12 1.4/1.2 1.6/1.4 1.6/1.4 1.8/1.4 2.0/1.6 2211.6 2.4/11.8 26/2.0
Nom. overall
cable dia
mm 23.0 24.6 280 31.2 35.3 38.4 426 46.8 52.7 598 66.6
Approx. weight kg/km 631 737 988 1246 1629 2020 2342 2931 3752 4729 5905
Armoured AYFY
Nom. overall
cable dia
mm 24.30 25.80 29.60 32.30 36.40 3950 44.10 4820 53.60 60.5 67.6
Approx. weight kg/km 984 1144 1446 1722 2189 2604 3084 3685 4541 5607 6907
Current carrying capacity
- In ground amps 76 92 110 135 165 185 210 235 275 305 335
- In air amps 70 86 105 130 155 180 205 240 280 315 375


1100 volts three core Unarmoured/Armoured Cable Type AYY/AYFY to IS : 1554 (part-I) 1988.
Nominal conductor
area
(sq.mm.) 16 25 35 50 70 95 120 150 185 240 300 400
Unarmoured AYY
Nom. insulation
thickness
mm 1.0 1.2 1.2 1.4 1.4 1.6 1.6 18 2.0 2.2 2.4 2.6
Nom. overall
cable dia
mm 20.3 24.2 26.0 30.7 32.8 38.2 39.6 43.7 49.5 55.5 629 71.6
Approx. weight kg/km 486 684 837 1128 1407 1876 2197 2669 3298 4207 5324 6782
Armoured AYFY
Nom. overall
cable dia
mm 21.50 25.40 27.30 31.80 33.90 39.30 41.10 44.70 50.40 56.60 63.60 72.60
Approx. weight kg/km 781 1049 1249 1596 1880 2460 2838 3314 4034 5052 6225 7861
Current carrying capacity
- In ground amps 60 76 92 110 135 165 185 210 235 275 305 335
- In air amps 51 70 86 105 130 155 180 205 240 280 315 375