Constructional and other details 1100 volts Single Core Unarmoured/Armoured Cable type: AYY/AYWaY to IS: 1554 (part-I) 1988.
Nominal
conductor area
(sq.mm.) 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
Unarmoured AYY
Nom. insulation
thickness
mm 1.20 1.20 1.20 1.40 1.60 1.60 1.80 200 2.20 2.40 2.60 3.00 3.40 3.40 3.40
Nom. overall
cable dia
mm 12.35 1320 1505 16.90 18.85 20.80 22.75 24.80 27.80 3030 34.40 38.10 42.75 46.60 5110
Approx. weight kg/km 187 225 289 372 477 584 708 847 1071 1297 1642 2065 2587 3157 38S6
Armoured AYWay
Nom. insulation
thickness
mm 1.50 1.50 no 170 1.90 190 2.10 2.30 2.S0 2.70 3.00 3.40 390 390 3.90
Nom. overall
cable dia
mm 15.15 1595 17.80 2000 22.35 2390 25.85 27.90 31.20 32.70 38.40 42.40 47.25 5110 56.60
Approx. weight kg/km 304 348 430 545 697 807 945 1108 1387 1650 2112 2609 3222 3842 4807
Current carrying capacity
- In ground amps 86 100 120 140 175 195 220 240 270 295 325 345 390 440 490
- In air amps 85 105 130 155 190 220 250 290 335 380 435 480 550 640 720


1100 volts three core Unarmoured/Armoured Cable Type A YY/A YFY to IS : 1554 (part-I).
Nominal conductor
area
(sq.mm.) 16 25 35 50 70 95 120 150 185 240 300 400
Unarmoured AYY
Nom. insulation
thickness
mm 1.00 1.20 1.20 1.40 1.40 1.60 1.60 180 2.00 2.20 2.40 2.60
Nom. overall
cable dia
mm 17.8 21.6 23.1 26.0 29.6 33.1 35.4 40.3 43.3 49.6 53.3 617
Approx. weight kg/km 375 540 651 839 - 1414 1683 2085 2494 3262 3990 5150
Armoured AYFY
Nom. overall
cable dia
mm 19.40 22.90 2440 27.60 30.80 34.20 36.90 41.80 44.40 50.80 54.50 62.40
Approx. weight kg/km 661 858 992 1268 1548 1916 2253 2734 3153 4037 4800 6037
Current carrying capacity
- In ground amps 60 76 92 110 135 165 185 210 235 275 305 335
- In air amps 51 70 86 105 130 15 180 205 240 280 315 375